Still exceeds 300 kVA transformer capacity.
Motor code letter = G (LRC = 5.6 kVA/HP) Starting kVA = 200 HP × 5.6 = 1120 kVA (full voltage) nema mg1-32 amp- 33
The document is divided into "Parts" and then numbered "Sections." Sections 32 and 33 fall under (General Concerning Definite-Purpose Motors) and Part 31 (General Concerning Integral-horsepower Motors), respectively. Part 2: Deep Dive into NEMA MG1-32 What is NEMA MG1-32? NEMA MG1-32 is titled: "Determination of Motor Input kVA at Starting and During Acceleration for Reduced Voltage Starting." Still exceeds 300 kVA transformer capacity
In simpler terms, this section defines the standard methods for calculating the apparent power (kVA) that a motor draws from the line —specifically when using reduced-voltage starting methods such as autotransformers, part-winding, or wye-delta starters. Why is MG1-32 Critical? When an induction motor starts, it draws a high inrush current (typically 600% of full-load current) for a few cycles, followed by a starting current (typically 500–600% of full-load amps) until it reaches full speed. This current, multiplied by the voltage, gives the starting kVA . NEMA MG1-32 is titled: "Determination of Motor Input
| Starting Method | % of Full Voltage | % of Starting Current | % of Starting Torque | % of Starting kVA | |----------------|------------------|----------------------|----------------------|--------------------| | Full Voltage | 100% | 100% | 100% | 100% | | Autotransformer (80% tap) | 80% | 80% | 64% | 64% | | Autotransformer (65% tap) | 65% | 65% | 42% | 42% | | Wye-Delta (Star-Delta) | 58% | 33% | 33% | 33% | | Part-Winding (50-100% winding) | 100% | 50-70% | 20-45% | 50-70% | Problem: A 100 HP, 460V, three-phase motor has a locked rotor current of 600A (Code G motor). Calculate the starting kVA using a wye-delta starter.
A reduced-voltage starter (MG1-32) reduces starting current (amps) and thus reduces the thermal stress (MG1-33) on the motor. However, it also increases acceleration time. A longer acceleration time may actually increase total heating, because the motor stays in high-slip (high current) region longer.
| NEMA Section | Focus | Key Parameter | Protection Device | |--------------|-------|---------------|-------------------| | MG1-32 | Starting kVA | Inrush current & voltage drop | Soft starter, reactor, autotransformer | | MG1-33 (AMP-33) | Thermal capacity | Current during acceleration & running | Overload relay, thermal model |